PMA Prozeß- und Maschinen-Automation GmbHUniversal controller for burnersKS40-1 burnerKS40-1 burnerKS40-1 burnerOperating manualEnglish9499-040-66011V

Seite 2 - General warning

Error status (error status 3 - 9 only with error AdA.H / AdA.C ):3.3 Self-tuningAfter starting by the operator, the controller makes a self-tuning att

Seite 3 - Contents

Self-tuning cancellation by the controller:If the Err LED starts blinking while self-tuning is running, successful self-tuningis prevented due to the

Seite 4 - KS40-1 burner 4

Values Tgand xmax(step change from 0 to 100 %) or Dt and D x (partial step re-sponse) can be used to determine the maximum rate of increase vmax.y =co

Seite 5 - 1 Mounting

3.5 Operating structureAfter supply voltage switch-on, the controller starts with the operating levels.The controller status is as before power off.gP

Seite 6 - 2 Electrical connections

4 Configuration level4.1Configuration with qUICAt configuration level, the controller function is determined by changing configu-ration word Con1 . Co

Seite 7 - 3.1 Front view

After exit from the configuration level (see page 43, the controller is re-initiali-zed (all display elements are lit) and changes over to normal oper

Seite 8 - Extended operating level

Function: 3-point signallerSettings:OUT1: Switch-on point is coupled with the set-point.Switching difference Sd1: in units of phys. quantity.OUT2: Swi

Seite 9 - Operation

Function: 3-point stepping controllerSettings:Controller: SH: in units of phys. quantityResponse threshold A: 0,5 w SHSwitching difference XSd : 0,06

Seite 10 - 3.3 Self-tuning

4.2 Configuration without qUIC ( qUIC= OFF)When key Ù is kept pressed during controller supply voltage switch-on, theconfiguration is switched off wit

Seite 11 - 3.4 Manual tuning

Configuration level19 KS40-1 burnerName Value range Description DefaultOwnsettingFAILBehavior at sensor break10Controller outputs switched of1y=Y22y =

Seite 12 - Formulas

© PMA Prozeß- und Maschinen-Automation GmbH • Printed in Germany (0207)All rights reserved. No part of this document may bereproduced or published in

Seite 13 - 3.5 Operating structure

Configuration levelKS40-1 burner 20InP.2Name Value range Description DefaultOwnsettingI.FncFunction selection of INP200No function2External set-point

Seite 14 - Configuration with qUIC

Configuration level21 KS40-1 burnerOut.1 / 2 / 3Name Value range Description DefaultOwnsettingO.ActMethod of operation of output OUT1Out.1:0Out.2:0Out

Seite 15 - Configuration level

Configuration levelKS40-1 burner 22Name Value range Description DefaultOwnsettingmAnAutomatic/manual switching60No function1Always active3DI2 switches

Seite 16 - Function: 3-point signaller

Configuration level23 KS40-1 burnerothrName Value range Description DefaultOwnsettingUnitUnit10Without unit1°C2°FdPDecimal point (max. number of digit

Seite 17

5 Parameter setting levelParameter setting levelKS40-1 burner 24CntrVisiblewith qUICName Value range Description DefaultOwnsettingfPb11...9999Proporti

Seite 18 - Configuration survey:

Parameter setting level25 KS40-1 burnerProGVisiblewith qUICName Value range Description Default Own settingSP.01-1999...9999Segment end set-point 1100

Seite 19

5.1 Input scaling (only visible with qUIC = OFF)When using current or voltage signals as input variables for InP.1 or InP.2,scaling of input and displ

Seite 20

6 Calibration levelgMeasured value correction ( CAL) is only visible if ConF / InP.1 / Corr = 1or 2 and qUIC = OFF is chosen.The measured value can be

Seite 21 - Out.1 / 2 / 3

Offset correction ( ConF/ InP.1 / Corr =1 ):InL.1: The input value of the scaling point is displayed.The operator must wait, until the process is at r

Seite 22

2-point correction ( ConF/ InP.1 / Corr =1 ):InL.1: The input value of the lower scaling point is displayed.The operator must adjust the lower input v

Seite 23

3 KS40-1 burnerContents1 Mounting ... 52 Electrical connections ... 63 Operation...

Seite 24 - 5 Parameter setting level

7 ProgrammerProgrammer set-up:For using the controller as a programmer, select parameter SP.Fn = 1 in theConF menu. The programmer is started via one

Seite 25 - Parameter setting level

+Program parameter changing while the program is running is possible.Changing the segment time:Changing the segment time leads to re-calculation of th

Seite 26

8 Technical dataINPUTSPROCESS VALUE INPUT INP1Resolution: > 14 bitsDecimal point: 0 to 3 digits behind thedecimal pointDig. input filter: adjustabl

Seite 27 - 6 Calibration level

OUTPUTSRELAY OUTPUTS OUT1, OUT2Contact type: 2 NO contacts withcommon connectionMax. contact rating: 500 VA, 250 V, 2A at48...62 Hz,resistive loadMin.

Seite 28 - Calibration level

GENERALHousingMaterial: Makrolon 9415flame-retardantFlammability class: UL 94 VO, self-extinguishingPlug-in module, inserted from the frontSafety test

Seite 29

Technical data35 KS40-1 burnerRange Input resistance Accuracy Resolution (Ô)0-10 Volt~ 110 kWß 0,1 % ß 0,6 mV0-20 mA49 W (voltage requirement ß 2,5 V)

Seite 30 - Programmer

9 Safety hintsThis unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 andwas delivered in safe condition.The unit complies with Euro

Seite 31

MAINTENANCE, REPAIR AND MODIFICATIONThe units do not need particular maintenance.aWarningWhen opening the units, or when removing covers or components

Seite 32 - T (OPTION)

9.1 Resetting to factory settingIn case of faultyconfiguration, KS4x-1 can be reset to the default condition.For this, the operator must keep the keys

Seite 33

39 KS40-1 burnerIndex0-92-point correction ...27CCalibration (CAL)...27Calibration level (CAL)...27-29Configuration withQUIC

Seite 34

KS40-1 burner 4

Seite 35 - Technical data

Subject to alterations without notice © PMA Prozeß- und Maschinen-Automation GmbHÄnderungen vorbehalten P.O.B. 310 229, D-34058 Kassel, GermanySous ré

Seite 36 - 9 Safety hints

1 MountingSafety switch:For access to the safety switches, the controller must be withdrawn from the hou-sing. Squeeze the top and bottom of the front

Seite 37 - Safety hints

2 Electrical connections* Safety switch INP1 (mA i 10V) in position 10V** Safety switch INP1 (mA i 10V) in position mA/PtConnection of input INP1Input

Seite 38 - 8.8.8.8

3 Operation3.1 Front viewgIn the upper display line, the process value is always displayed. At parameter,configuration, calibration as well as extende

Seite 39 - QUIC Codes ...14

3.2 Operating levelThe content of the extended operating level is determined by means of BlueCon-trol (engineering tool). Parameters which are used fr

Seite 40 - 9499- 040- 66011

Maintenance manager / Error listWith one or several errors, the extended operating levelalways starts with the error list. Signalling an actual en-try