PMA Prozeß- und Maschinen-Automation GmbHTB 45Temperature monitorTB 45TB 45Operating manualEnglish9499-040-71911valid from: 02/2012railline
3.1 ConnectorsThe four instrument connectors are of the plug-in type. They plug into the housing from top or bottom and click in posi-tion (audible la
.4 Electrical connections4.1 Connecting diagram4.2Terminal connectionsaFaulty connection can lead to the destruction of the instrument.1 Connecting th
3 Connecting input di1Digital input, configurable as a switch or a push-button.a contact input terminals: 7, 8b optocoupler input (optional) terminals
4.3 Connecting diagramThe instrument terminals used for the engineering can be displayed and printed out via BlueControl®( menu File \ Printpreview -
4.4 Connection examplesElectrical connections14 Connection examples TB 45INP2INP1PWROUT3di1L1N11413121716151118PWR87632154+FuseheatingINP1PWRLCdi11413
4.5 Hints for installation•Measurement and data lines should be kept separate from control and power supply cables.•Sensor measuring cables should be
.5 Operation5.1 Front view1 Display line 1: process value or limit value LC2 Display line 2: limit value LC / unit /extended operating level/ error li
5.2 Operating structureOperation of the unit is divided into four levels:With TB 45, access to parameter setting, configuration and calibration level
5.4 Displays at operating level5.4.1 Display line 1The value shown on display line 1 can be determined by configuration Dis1. This configuration is ad
5.4.3 Switching over by means of the Enter keyVarious values can be called up on display line 2 by pressing the Enter key.1The value defined for displ
© 2004 · PMA Prozeß- und Maschinen-Automation GmbH Printed in GermanyAll rights reserved · No part of this document may be reproduced or published in
5.6 Release functionThe following settings for error list resetting or limiting function releasing are available:•Resetting via digital input di1•Rese
.6 FunctionsThe signal data flow of temperature monitor TB 45 is shown in the following diagram:6.1 Limiting functionsTB 45 can be configured for vari
6.2 LinearizationThe input values of input INP1 or INP2 can be linearized via a table (dependent from adjusted sensor type S.tYP).By means of tables,
gWhen using current or voltage signals as input variables for InP.x, the input and display valuesshouldbe scaled at the parameter level. Specification
aFor using the pre-defined scaling with thermocouples and resistance thermometers (Pt100), the settings forInL and OuL as well as for InH and OuH must
6.4 FilterA first order mathematic filter can be used for the input values. The time constant is adjustable. This low-pass filter isused for suppressi
gWith O2 measurement, specification if parameters related to the measured value should be output in ppmor % is required. This is done centrally during
Each of the 2 pre-alarms Lim.2 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched offindividually (parameter = “OFF”). The sw
6.6.1 Monitoring the number of operating hours and switching cyclesOperating hoursThe number of operating hours can be monitored. When reaching or exc
Parameter O.Src defines the signal source of the output value.Example:O.Src = 3 signal source for Out.3 isthe process valueScaling of the output range
TB 45 3Content1. General51.1 Application in thermal plants...62. Safety hints ...72.1
6.7.3 Transmitter supply (optional)With setting O.typ = 5, two-wire transmitter supply is possible via output OUT3.In this case, the analog output of
6.8 Maintenance manager / error listIn case of one or several errors, the error list is always displayed at thebeginning of the extended operating lev
gWhen an alarm is still pending, i.e. unless the error cause was removed (E display blinks), latched alarmscannot be acknowledged and reset.6.9 Reset
.7 Configuration level7.1 Configuration surveyDisplay suppression of configuration data dependent on instrument version and other configuration settin
7.2 ConfigurationDependent on instrument version and configuration settings, display of values which are not required is suppressed.µ The entries mark
Name Value range Description47Special (-200..200 mV)50Potentiometer 0...160 Ohm51Potentiometer 0...450 Ohm52Potentiometer 0...1600 Ohm53Potentiometer
Name Value range DescriptionFnc.2(Fnc.3)Function of pre-alarm2/30switched off1Measured value monitoringIf a limit is exeeded an alarmsignal is execute
Name Value range DescriptionOut.0-1999...9999Scaling 0% (only for Out.3 analog) µLower analog output scaling limit (corresponds to 0%). When using cur
Name Value range DescriptiondELY0...200Response delay [ms] µS.IFEnable system interface µ0The system interface is de-activated.1The system interface i
Name Value range DescriptionICnfBlockierung Konfigurationsebene (nur mit BlueControl sichtbar!)0Released1BlockedICalBlock calibration level (only visi
4 TB 457. Configuration level ...337.1 Configuration survey ...337.2 Configuration ...
.8 Parameter level8.1 Parameter surveyDependent on device version und adjusted configurations values not needed become hidden.8.2 Adjustment•Parameter
8.3 Parameter levelµ Entrys marked with this symbol are selectable only with existing device-option.Range rnGName Value range DescriptionrnG.L-1999...
.9 Calibrating levelIn the calibration menu ( CAL) the measured value can be adjusted.aPlease, note that the input value may be shifted when handling
9.1 Offset correctionThe offset-correction shifts the input value by a pre-defined value.Parameter setting:( ConF/ InP/ Corr =1 )wOn-line offset corre
9.2 2-point correction2-point correction can change the offset and gradient ofthe input curve.Parameter setting:( ConF/ InP/ Corr = 2 ):w2-point corre
.10 BlueControlengineering toolThe Engineering Tool BlueControl is the projecting environment for the BluePort controller series as for the railline f
.11 VersionsAccessories delivered with the unit:•Operating note•Rail-to-bus connector forthe interface optionAdditional equipment with orderingdata.Ve
.12 Technical dataINPUTSUNIVERSAL INPUT INP1Type: single-ended, except thermocouplesResolution: > 14 bitsDecimal point: 0 to 3 decimalsDigital inpu
Technical data48 TB 45CONTROL INPUT DI1 (RESET)Configurable as direct or inverse switch or push button!Contact inputConnection of potential-free conta
Load effect: ß 0,02%Resolution: ß 1,5 úAError: ß 0,1%Voltage output0/2...10V, configurablenot continuously short-circuit proofControl range: -0,15...1
.1 GeneralThank you very much for buying a TB 45 temperature monitor.TB 45 temperature monitor are used for process monitoring. The units provide proc
ENVIRONMENTAL CONDITIONSProtection classesFront panel: IP 20Housing: IP 20Terminals: IP 20Permissible temperaturesFor specified accuracy: -10...55°CWa
TB 45 51.13 IndexIndex!2-point-correction 44AAccessories 46Additional equipment 46Analog output 28 - 30Applications 5BBehaviour after supply v. on 17C
Subject to alterations without notice © PMA Prozeß- und Maschinen-Automation GmbHÄnderungen vorbehalten P.O.B. 310 229, D-34058 Kassel, GermanySous ré
1.1 Application in thermal plantsIn many thermal plants, only the use of approved control instruments is permissible.There is a TB 45 version (TB45-1x
.2 Safety hintsThis unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 and was delivered in safe condition.The unit complies with Eu
2.1 Maintenance, repair, modificationThe units do not need particular maintenance.There are no operable elements inside the device, so the user must n
.3 MountingThe unit is provided for vertical mounting on 35 mm top-hat rails to EN 50022.If possible, the place of installation should be exempt of vi