18-DINDUAL COLOUR DISPLAYTEMPERATURE INDICATORProduct Manual59135-2
2.4 PARAMETER SEQUENCEThe Program Mode parameter sequence is as follows:2 -3 Volume I OM090-259135ParameterDescription (PrimaryDisplay)Parameter Descr
3 SERIAL COMMUNICATIONSThe Serial Communications option is a standard RS485 communications link. Up to 32 standard RS485 loads may be presented to a s
3.3.1 Form 1 MessageThe master device sends a Form 1 message to ascertain whether a specificcommunications address is occupied by an instrument. If th
3.3.3 Form 3 MessageThis message implements the Parameter Write operation either on a singleaddressed instrument (address in the range 1 - 99) or broa
3.4 ERROR CONDITIONSIf a slave device detects a syntax error or parity error, it will not reply to themessage; the master device should make up to two
18-DIN DUAL COLOUR DISPLAYTEMPERATURE INDICATORProduct ManualContents - Volume IIThe procedures described in this Volume must be undertaken only bytec
AppendicesA PRODUCT SPECIFICATION A-1A.1 DISPLAY A-1A.2 SENSOR INPUT A-1A.3 DIGITAL INPUT (OPTION) A-3A.4 TRANSISTOR OUTPUTS A-3A.5 RELAY 1 OUTPUT A-3
1 INSTALLATION1.1 UNPACKING1. Remove the Indicator from its packing. The indicator is supplied with apanel gasket and push-fit fixing strap. Retain th
1.3 CONNECTIONS AND WIRINGThe rear terminal connections are shown in Figure 1 -4 .1 -2 Volume II PM090-159135Figure 1-3 Panel-mounting
PM090-1 Volume II 1-359135Figure 1-4 Rear Terminal Connections
HOW TO USE THIS MANUALThis manual comprises two volumes:
1.3.1 Mains (Line) SupplyThe Indicator will operate on 90 - 264V AC 50/60Hz mains (line) supply. The powerconsumption is approximately 4 watts.CAUTION
1.3.5 Digital Input OptionTerminals 16 and 17, when this option is fitted, may be used for external selectionof the Security facility) which allows/pr
Where several Indicators are connected to one master port, the master porttransceiver in the active state should be capable of driving a load of 120k
2 INTERNAL LINKS AND SWITCHES2.1 REMOVING THE INDICATOR FROM ITS HOUSINGCAUTION: Before removing the Indicator from its housing, ensure thatall power
2-2 Volume II PM090-259135Figure 2-2 Removing the Relay 2/Linear Output Options PCBs
2.2 REMOVING/REPLACING THE RELAY 2/LINEAR OUTPUT OPTION PCBsWith the Indicator removed from its housing:1. Gently push the rear ends of the CPU PCB an
2.4 REPLACING THE INSTRUMENT IN ITS HOUSINGTo replace the instrument in its housing, simply align the CPU PCB and PowerSupply PCB with their guides an
3 CONFIGURATION MODE3.1 ENTRY/EXITUse these keys in the same way to exit from Configuration Mode.3.2 PARAMETER SELECTION3.2.1 With Help Facility Enabl
3.2.2 With Help Facility Disabled3.3 EDITING THE DISPLAYED PARAMETER3-2 Volume II PM090-359135
3.4 PARAMETER SEQUENCEPM090-3 Volume II 3-359135ParameterDescription (PrimaryDisplay)Parameter Description Adjustment RangeInputRangeSelects the input
18-DIN DUAL COLOUR DISPLAYTEMPERATURE INDICATORProduct ManualContents - Volume I1 OPERATION MODE 1-11.1 FRONT PANEL 1-11.2 PARAMETER SEQUENCE 1-21.3 I
3-4 Volume II PM090-359135ParameterDescription (PrimaryDisplay)Parameter Description Adjustment RangeOutput 2UsageDetermines how NPNOutput 2 and Relay
PM090-3 Volume II 3-559135Input Type Range Code Range Minimum Range MaximumThermocouple InputsJ100 (°C)101 (°F)110 (°C)111 (°F)–200–328–128.0–198.4120
4 SERIAL COMMUNICATIONS -CONFIGURATION MODEThis section is a supplement to the information provided in Volume I, Section 3 and describes the Read/Wri
PM090-4 Volume II 4-259135Identifier Hex. Parameter Adjustment Rangel 6C Output 1 Use 0 Alarm 1 non-latching,direct action1 Alarm 1 non-latching,rever
4-3 Volume II PM090-459135Input Type Range Code Range Minimum Range Maximum Hex. ValueThermocouple InputsJ100 (°C)101 (°F)110 (°C)111 (°F)–200–328–128
APPENDIX A PRODUCT SPECIFICATIONA.1 DISPLAYType: Red/green, seven-segment LED, five-digitprimary display, one-digit secondarydisplay.Height: 0.71 inch
A-2 Volume II PM090-A59135Input Type Range Code Range Minimum Range MaximumThermocouple InputsJ100 (°C)101 (°F)110 (°C)111 (°F)–200–328–128.0–198.4120
A.3 DIGITAL INPUT (OPTION)Type: Voltage-free or TTL-compatible operation.May be connected to: External switch/relay contacts orTTL-compatible logic si
Lifetime: >500,000 operations at ratedvoltage/current.Isolation: InherentA.6 RELAY 2 OUTPUT (OPTION)Contact Type: Single pole double throw.Rating:
A.9 PERFORMANCEReference ConditionsAmbient Temperature:20°C ±2°CRelative Humidity: 60 - 70%Supply Voltage: 90 - 264V AC 50HzSource Resistance: <10Ω
1 OPERATION MODEThis mode covers day-to-day operation of the Indicator.1.1 FRONT PANEL1-1 Volume I OM090-159135Key/Display/Indicator FunctionDown key
Relative Humidity: 20% - 95% non-condensingSource Resistance: 1000 Ω maximum (thermocouple)Lead Resistance: 50Ω per lead maximum balanced (Pt100)Perfo
1.2 PARAMETER SEQUENCEOM090-1 Volume I 1-259135
1.3 INPUT OVER-RANGE OR UNDER-RANGEIf the input becomes over-range or under-range, the primary display will show:The display will disappear when the i
1.6 RESETTING A LATCHED ALARMIf Relay 1 is configured to act as a latched Alarm 1 relay, when this alarm isactive, it can be reset by selecting the pr
2 PROGRAM MODE2.1 ENTRY/EXITUse the Program (PGM) key in the same way to exit Program Mode (i.e. return toOperation Mode).2.2 PARAMETER SELECTION2.2.1
2.2.2 With Help Facility Disabled2.3 EDITING THE DISPLAYED PARAMETER (EDIT MODE)OM090-2 Volume I 2-259135